1. Whenever possible the delivery reel should be transported to the installation site. Avoid rolling the reel. If the reel cannot be mounted directly on the equipment the
cable should be unreeled with the aid of idle pulleys and
a drag rope. 2. During unreeling the cable must be taken only from
revolving reels and only from the top while ensuring that 3. Before installation the cable must be laid out and
stretched. If this is not possible it is essential to keep the 4. The cable must be spooled onto the equipment reel
without twisting. It is equally important to avoid twisting 5. lt is essential to use properly sized clamps (length 4x cable diameter) for fastening the cable ends in order to prevent crushing. The length of cable left unreeled before the fastening point must be at least 40x diameter, but it is advisable to use a compensating pulley here also. 6. At least two coils must remain on the equipment reel when the cable has run out. 7. For cables with an outer diameter of up to 21.5 mm the inner bending diameter should not be less than 10x and above that figure, 12.5 x the cable diameter. 8. S-bends in the cable must be avoided. However, if this is
not possible, the center spacing must be as shown 10. The static continuous tensile stress should not exceed
15 N/mm2 of the total copper cross section and the 11. The actual current rating in continuous operation is
limited by: |
|
||